Ghassemi, F., Dennis, S., Ainsley, A., Haddad, A. Manu ORCID: https://orcid.org/0000-0003-4153-6146 and Robson, S. ORCID: https://orcid.org/0000-0003-3156-1487 2018. 275 kV cable discharge field measurement and analysis of SVLs chain failure using ATP. Electric Power Systems Research 161 , pp. 95-102. 10.1016/j.epsr.2018.04.009 |
Preview |
PDF
- Accepted Post-Print Version
Available under License Creative Commons Attribution Non-commercial No Derivatives. Download (763kB) | Preview |
Abstract
Results of field measurement of trapped charges on a 275 kV cable will be presented. The instrumentation and calibration method used in the measurement will be discussed. It will be shown that if the cable is not force-discharged by means of earth switches, the trapped charges will decay very slowly. The atmospheric parameters such as humidity and temperature affect the discharge time, which also depends on how much of the circuit is exposed to open air. The measurement results are used in EMTP-ATP simulation to confirm that trapped charges may be sufficient to cause sheath voltage limiters (SVL) of the cable to fail. The number of SVL breakdown depends on the mode of SVL failure, i.e. whether it attains low impedance (short circuit) or open circuit when the energy absorbed exceeds the rating.
Item Type: | Article |
---|---|
Date Type: | Publication |
Status: | Published |
Schools: | Engineering |
Publisher: | Elsevier |
ISSN: | 0378-7796 |
Date of First Compliant Deposit: | 8 October 2018 |
Date of Acceptance: | 9 April 2018 |
Last Modified: | 10 Nov 2024 16:15 |
URI: | https://orca.cardiff.ac.uk/id/eprint/112472 |