Grid side unbalanced fault detection using soft open point in an electrical distribution network

Aithal, Avinash, Li, Gen ORCID: https://orcid.org/0000-0002-0649-9493 and Wu, Jianzhong ORCID: https://orcid.org/0000-0001-7928-3602 2017. Grid side unbalanced fault detection using soft open point in an electrical distribution network. Energy Procedia 105 , pp. 2859-2864. 10.1016/j.egypro.2017.03.631

[thumbnail of 1-s2.0-S1876610217306859-main.pdf]
Preview
PDF - Published Version
Available under License Creative Commons Attribution Non-commercial No Derivatives.

Download (440kB) | Preview

Abstract

Soft open point (SOP) is a power electronic device that installed in place of normally open points in distribution networks. This paper investigates the performance of SOP under an unbalanced line to ground (L-G) fault in a medium voltage (MV) distribution network. A method to detect unbalanced grid side AC faults was developed using positive and negative sequence currents injected into the feeder by the SOP. Simulations were carried out on a network model developed in PSCAD/EMTDC. Local measurements at SOP grid connection point were used to define a fault index. Results show that the fault index, based on the values of positive and negative sequence currents, is able to effectively detect the presence of an unbalanced fault in a MV distribution network.

Item Type: Article
Date Type: Publication
Status: Published
Schools: Engineering
Publisher: Elsevier
ISSN: 1876-6102
Date of First Compliant Deposit: 31 July 2018
Last Modified: 22 Mar 2024 07:22
URI: https://orca.cardiff.ac.uk/id/eprint/113618

Citation Data

Cited 10 times in Scopus. View in Scopus. Powered By Scopus® Data

Actions (repository staff only)

Edit Item Edit Item

Downloads

Downloads per month over past year

View more statistics