Li, Gen ![]() ![]() ![]() ![]() ![]() |
Preview |
PDF
- Published Version
Available under License Creative Commons Attribution. Download (2MB) | Preview |
Abstract
Although the probability of occurrence of station internal ac grounding faults in modular multilevel converter (MMC)-based high-voltage direct-current systems is low, they may lead to severe consequences that should be considered when designing protection systems. This paper analyzes the characteristics of valve-side single-phase-to-ground (SPG) faults in three configurations of MMC systems. Fault responses for symmetrical monopole MMCs are first studied. Upper arm overvoltages and ac-side nonzero-crossing currents arising from SPG faults in asymmetrical and bipolar configurations are then investigated. DC grounding using an LR parallel circuit is employed to create current zero-crossings, which will enable the operation of grid-side ac circuit breakers. The theoretical analysis is verified through simulations performed in PSCAD/EMTDC, with simulation results and the theoretical analysis showing a good agreement. The studies in this paper will be valuable for the design of protection systems for station internal ac grounding faults.
Item Type: | Article |
---|---|
Date Type: | Publication |
Status: | Published |
Schools: | Engineering |
Publisher: | Institute of Electrical and Electronics Engineers (IEEE) |
ISSN: | 0278-0046 |
Date of First Compliant Deposit: | 26 April 2019 |
Date of Acceptance: | 6 April 2018 |
Last Modified: | 07 May 2023 00:57 |
URI: | https://orca.cardiff.ac.uk/id/eprint/121955 |
Citation Data
Cited 4 times in Scopus. View in Scopus. Powered By Scopus® Data
Actions (repository staff only)
![]() |
Edit Item |