Cardiff University | Prifysgol Caerdydd ORCA
Online Research @ Cardiff 
WelshClear Cookie - decide language by browser settings

Non-contact measurement and analysis of trapped charge decay rates for cable line switching transients

Robson, Stephen ORCID: https://orcid.org/0000-0003-3156-1487, Haddad, Abderrahmane ORCID: https://orcid.org/0000-0003-4153-6146, Dennis, Simon and Ghassemi, Foroozan 2020. Non-contact measurement and analysis of trapped charge decay rates for cable line switching transients. Energies 13 (5) , 1142. 10.3390/en13051142

[thumbnail of energies-13-01142.pdf] PDF - Published Version
Available under License Creative Commons Attribution.

Download (5MB)

Abstract

During reclosure of 275 kV cable circuits used for voltage control, excessive overvoltages were observed on the network. Such events cause onerous and costly failures. Transient simulations have shown that the normal voltage on its own cannot generate such excessive switching overvoltages. Initial investigations by the network operator pointed towards trapped charge on the unearthed as the cause of the failures. Measurement of these trapped charge voltages and their slow decay without interfering with the charge has, to the author’s knowledge, not been done before in an operational substation. This work introduces a technique to measure trapped charge at a 275 kV substation using the Electrostatic Field Mill. Since the electric field is a proxy measurement of surface voltage, field mills can also be used to measure voltage. In this paper, an on-site substation measurement setup using an electrostatic field mill has been developed for the non-contact measurement of trapped charge voltage on a 275 kV underground cable circuit following switching operations at a National Grid substation. Results of field measurements within the substation and laboratory experimentation are discussed. It is demonstrated that with adequate calibration, achieved by using the known pre-switching power frequency steady state voltage, the slowly decaying DC voltage caused by the cable trapped charge can be measured using this non-contact technique. The correlation between the instantaneous time constant and the relative humidity is also analysed.

Item Type: Article
Date Type: Publication
Status: Published
Schools: Engineering
Additional Information: This is an open access article distributed under the Creative Commons Attribution License which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Publisher: MDPI
ISSN: 1996-1073
Date of First Compliant Deposit: 4 March 2020
Date of Acceptance: 27 February 2020
Last Modified: 25 Sep 2023 16:23
URI: https://orca.cardiff.ac.uk/id/eprint/130126

Citation Data

Cited 2 times in Scopus. View in Scopus. Powered By Scopus® Data

Actions (repository staff only)

Edit Item Edit Item

Downloads

Downloads per month over past year

View more statistics