Li, Chuanyue ORCID: https://orcid.org/0000-0001-6835-6642, Wang, Sheng ORCID: https://orcid.org/0000-0002-2258-2633 and Liang, Jun ORCID: https://orcid.org/0000-0001-7511-449X 2022. Tuning method of a grid-following converter for the extremely-weak-grid connection. IEEE Transactions on Power Systems 37 (4) , pp. 3196-3172. 10.1109/TPWRS.2022.3167899 |
Preview |
PDF
- Accepted Post-Print Version
Download (1MB) | Preview |
Abstract
This paper proves that a grid-following converter can stably connect to a weak grid even short-circuit ratio (SCR) is 1. Root instability causes of this grid-following control are identified including fast control response, insufficient damping, and slow voltage support. A simple and effective tuning guideline is proposed to stabilize this connection. Three control modes are considered in this tuning guideline including current control, active power and voltage (PV) control, and active power and reactive power (PQ) control . The switching model of a two-level converter is used for the simulation validation.
Item Type: | Article |
---|---|
Date Type: | Publication |
Status: | Published |
Schools: | Engineering |
Publisher: | Institute of Electrical and Electronics Engineers |
ISSN: | 0885-8950 |
Date of First Compliant Deposit: | 20 May 2022 |
Date of Acceptance: | 30 March 2022 |
Last Modified: | 25 Nov 2024 15:15 |
URI: | https://orca.cardiff.ac.uk/id/eprint/149627 |
Citation Data
Cited 1 time in Scopus. View in Scopus. Powered By Scopus® Data
Actions (repository staff only)