Transient analysis during switching of mechanically switched capacitor and damping network (MSCDN)

Hamid, H. A., Harid, Noureddine ORCID: https://orcid.org/0000-0001-8203-1895 and Haddad, Abderrahmane ORCID: https://orcid.org/0000-0003-4153-6146 2010. Transient analysis during switching of mechanically switched capacitor and damping network (MSCDN). Presented at: 45th International Universities Power Engineering Conference, Cardiff, UK, 31 August - 3 September 2010. 2010 45th International Universities Power Engineering Conference (UPEC 2010). London: Institute of Electrical and Electronics Engineers (IEEE), pp. 478-481.

Full text not available from this repository.

Abstract

This paper presents computation results of transient stresses during energization of an MSCDN in a 400 kV system. For validation purposes, transient voltages and currents were also estimated analytically before performing a full three-phase simulation using ATP/EMTP program. Following the circuit breaker closing, instantaneous overvoltage changes of high magnitude are observed across the reactor of MSCDN and the rate of rise of these overvoltages was examined. It is known that uniform distribution of such an impulsive voltage across the reactor windings is very unlikely. Consequently, the reactor is susceptible to insulation failure especially in the inter-turn regions

Item Type: Conference or Workshop Item (Paper)
Date Type: Publication
Status: Published
Schools: Engineering
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Publisher: Institute of Electrical and Electronics Engineers (IEEE)
ISBN: 9781424476671
Last Modified: 21 Oct 2022 10:17
URI: https://orca.cardiff.ac.uk/id/eprint/39759

Citation Data

Cited 4 times in Scopus. View in Scopus. Powered By Scopus® Data

Actions (repository staff only)

Edit Item Edit Item