Abd-Rahman, R., Haddad, A. ORCID: https://orcid.org/0000-0003-4153-6146, Kamarudin, M. S., Yousof, M. F. M. and Jamail, N.A.M.
2017.
Dynamic modelling of polluted outdoor insulator under wet weather conditions.
Presented at: 2016 IEEE International Conference on Power and Energy (PECon),
Melaka, Malaysia,
28-29 November 2016.
2016 IEEE International Conference on Power and Energy (PECon), Proceedings.
IEEE,
p. 610.
10.1109/PECON.2016.7951633
|
Abstract
This paper proposes a dynamic pollution modelling for evaluating electric field distribution over the composite insulator surface. Axial-symmetric insulator profile under wet contaminated conditions was developed and analysed using Finite Element Method (FEM) software. A nonlinear field-dependent conductivity with simplified assumptions was established to characterise the electrical properties of the pollution layer. Comparative studies showed that simulation of the proposed pollution model results in a more realistic electric field profile, offering better understanding on how the electric field behaves under various wet and contaminated conditions.