Aithal, Avinash and Wu, Jianzhong ORCID: https://orcid.org/0000-0001-7928-3602
2017.
Operation and performance of a medium-voltage DC link.
CIRED - Open Access Proceedings Journal
2017
(1)
, pp. 1355-1358.
10.1049/oap-cired.2017.0946
|
Abstract
The operation of a voltage source converter (VSC)-based medium-voltage (MV) direct current (DC) link is described. The use of a DC link in an MV distribution network is presented, considering salient similarities and differences to a high-voltage DC link. A PSCAD/EMTDC model was used to demonstrate the dynamic operation of an MVDC link, under normal and faulted network conditions. The study shows that MVDC can provide flexibility in a distribution network by decoupling real (P) and reactive (Q) power flows through the link, under normal operation. During a fault, however, the current injected from the converter could interfere with the detection and discrimination of AC system faults, in distribution networks with current-based protection scheme.
| Item Type: | Article |
|---|---|
| Date Type: | Publication |
| Status: | Published |
| Schools: | Schools > Engineering |
| Publisher: | IET |
| ISSN: | 2515-0855 |
| Last Modified: | 25 Oct 2022 13:47 |
| URI: | https://orca.cardiff.ac.uk/id/eprint/120770 |
Citation Data
Cited 11 times in Scopus. View in Scopus. Powered By Scopus® Data
Actions (repository staff only)
![]() |
Edit Item |





Dimensions
Dimensions