Su, Hongzhi, Wang, Chengshan, Li, Peng, Liu, Zhelin, Yu, Li and Wu, Jianzhong ORCID: https://orcid.org/0000-0001-7928-3602 2019. Optimal placement of phasor measurement unit in distribution networks considering the changes in topology. Applied Energy 250 , pp. 313-322. 10.1016/j.apenergy.2019.05.054 |
Abstract
Distribution networks usually have a meshed structure but are operated radially to improve the operating efficiency and ensure the power supply under an emergency situation. It is of great significance to guarantee the observability of the entire system under the topology changes in operation. This paper proposes an optimal placement method of phasor measurement unit (PMU) for distribution networks. A generalized binary integer linear programming (ILP) model for PMU placement is proposed. The changes in topology are considered to guarantee the observability under any possible operation mode. The existence of zero injection nodes (ZINs), the existing measurements, and their relevance are also covered in the proposed method to reduce the installed PMU number. The objective of the ILP problem is weighted by the degree of the corresponding node to obtain a scheme with higher measurement redundancy. The correctness and effectiveness of the proposed method are verified via case studies on the IEEE 33-node test feeder, PG&E 69-node test feeder, and a medium voltage distribution network in Southern China.
Item Type: | Article |
---|---|
Date Type: | Publication |
Status: | Published |
Schools: | Engineering |
Publisher: | Elsevier |
ISSN: | 0306-2619 |
Date of Acceptance: | 3 May 2019 |
Last Modified: | 04 Nov 2022 12:21 |
URI: | https://orca.cardiff.ac.uk/id/eprint/122746 |
Citation Data
Cited 28 times in Scopus. View in Scopus. Powered By Scopus® Data
Actions (repository staff only)
Edit Item |