Rashwan, Ahmed and Reid, Alistair ORCID: https://orcid.org/0000-0003-3058-9007 2023. Improved methods for UHF localization of partial discharge in air-insulated substations. Energies 16 (10) , 4221. 10.3390/en16104221 |
Preview |
PDF
- Published Version
Available under License Creative Commons Attribution. Download (4MB) | Preview |
Abstract
A time-difference-of-arrival-based partial discharge (PD) location system that utilises prior knowledge of substation layout is presented. We propose a new time delay estimator that employs onset detection techniques and demonstrate, through experimental results, that it is at least 2.8 times more accurate than other conventional estimators. Using knowledge of a substation’s layout, we develop a minimum mean-square-error (MMSE)-based location estimator and an algorithm that optimises antenna placement to maximise location accuracy in regions occupied by high-voltage equipment. Simulation results show that a system that uses the proposed techniques is 5.9 times more accurate than a more conventional system in a high-noise environment.